5-10
User Constant Tables
A: Setup Settings
Initialize Mode: A1
Con-
stant
Number
Name Description
Setting
Range
Factory
Setting
Change
during
Opera-
tion
Access
Level
MEMO-
BUS
Register
Page
A1-00
Language selec-
tion for Digital
Operator display
Used to select the language dis-
played on the Digital Operator
JVOP-160 only.
0: English
1: Japanese
2: German
3: French
4: Italian
5: Spanish
6: Portuguese
This constant is not changed by the
initialize operation.
0 to 6 0 Yes A 100H –
A1-01
Constant access
level
Used to set the constant access level
(set/read.)
0: Monitoring only (Monitoring
drive mode and setting A1-01
and A1-04.)
1: Used to select user constant
(Only constants set in A2-01 to
A2-32 can be read and set.)
2: Advanced
(Constants can be read and set in
both, quick programming mode
(Q) and advanced programming
(A) mode.)
0 to 2 2 Yes A 101H
6-109
6-110
A1-03 Initialize
Used to initialize the constants
using the specified method.
0: No initializing
1110: Initializes using the user
constants that have been
stored before using o2-03
parameter
2220: Initializes using a two-wire
sequence. (Initializes to the
factory setting.)
3330: Initializes using a three-
wire sequence.
0 to
3330
0 No A 103H –
A1-04 Password
Password input when a password
has been set in A1-05.
This function write-protects con-
stants of the initialize mode.
If the password is changed, A1-01
to A1-03 and A2-01 to A2-32 con-
stants can only be changed after
inputting the right password.
0 to
9999
0 No A 104H 6-109