5-12
Application Constants: b
Operation Mode Selections: b1
Con-
stant
Number
Name Description
Setting
Range
Factory
Setting
Change
during
Opera-
tion
Access
Level
MEMO-
BUS
Register
Page
b1-01
Reference source
selection
Sets the frequency reference input
method.
0: Digital Operator
1: Control circuit terminal (analog
input)
2: MEMOBUS communications
3: Option Card
0 to 3 1 No Q 180H
6-5
6-51
b1-02
RUN command
source selection
Sets the run command input
method.
0: Digital Operator
1: Control circuit terminal (digital
multifunktion inputs)
2: MEMOBUS communications
3: Option Card
0 to 3 1 No Q 181H
6-9
6-51
b1-03
Stopping method
selection
Used to set the stopping method
used when a stop command is input.
0: Deceleration to stop
1: Coast to stop
2: DC injection braking stop (Stops
faster than coast to stop, no
regenerative operation.)
3: Coast to stop with timer (Run
commands are disregarded
during deceleration.)
0 to 3 0 No Q 182H 6-11
b1-04
Prohibition of
reverse operation
0: Reverse enabled
1: Reverse disabled
2: Output Phase Rotation (both
rotational directions are enab-
led)
3: Output Phase Rotation with
Reverse prohibited.
0 to 3 0 No A 183H 6-37
b1-07
Operation selec-
tion after switch-
ing to remote
mode
Used to set the operation mode by
switching to the Remote mode
using the Local/Remote Key.
0: Run signals that are input during
mode switching are disregarded.
(Input Run signals after
switching the mode.)
1: Run signals become effective
immediately after switching to
the Remote mode.
0 or 1 0 No A 186H
b1-08
Run command
selection in pro-
gramming modes
Used to set an operation interlock in
programming modes.
0: Cannot operate.
1: Can operate (Disabled when
Digital Operator is set to select
run command (when b1-02 =
0)).
0 or 1 0 No A 187H
b1-11 RUN delay
Sets the delay time for the internal
RUN command.
0 to
600s
0 s No A 1DFH
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com

Table of Contents

Other manuals for YASKAWA Varispeed E7

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the YASKAWA Varispeed E7 and is the answer not in the manual?

YASKAWA Varispeed E7 Specifications

General IconGeneral
BrandYASKAWA
ModelVarispeed E7
CategoryDC Drives
LanguageEnglish

Related product manuals