5-26
Terminal Function Constants: H
Multi-function Contact Inputs: H1
* The values in parentheses indicate initial values when initialized in 3-wire sequence.
Multi-function Contact Input Functions
Con-
stant
Number
Name Description
Setting
Range
Factory
Setting
Change
during
Opera-
tion
Access
Level
MEMO-
BUS
Register
Page
H1-01
Terminal S3 func-
tion selection
Multi-function contact
input 1
0 to 6F 24 No A 400H –
H1-02
Terminal S4 func-
tion selection
Multi-function contact
input 2
0 to 6F 14 No A 401H –
H1-03
Terminal S5 func-
tion selection
Multi-function contact
input 3
0 to 6F
3 (0)
*
No A 402H –
H1-04
Terminal S6 func-
tion selection
Multi-function contact
input 4
0 to 6F
4 (3)
*
No A 403H –
H1-05
Terminal S7 func-
tion selection
Multi-function contact
input 5
0 to 6F
6 (4)
*
No A 404H –
Setting
Value
Function
Page
0 3-wire sequence (Forward/Reverse Run command) 6-10
1 Local/Remote selection (ON: Operator, OFF: Constant b1-01/b1-02 setting) 6-51
2 Operation Source Option Card/Inverter selection (ON: Option Card) 6-60
3
Multi-step speed reference 1
When H3-09 is set to 2, this function is combined with the master/auxiliary speed switch.
6-7
4 Multi-step speed reference 2 6-7
6 Jog frequency command (higher priority than multi-step speed reference)
6-7
6-51
7 Accel/decel time 1 6-16
8 External baseblock NO (NO contact: Baseblock at ON)
6-52
6-43
9 External baseblock NC (NC contact: Baseblock at OFF)
6-52
6-43
A Acceleration/deceleration ramp hold (ON: Acceleration/deceleration stopped, frequency is hold) 6-53
C Multi-function analog input A2 disable/enable (ON: Enable) 6-52
F Not used (Set when a terminal is not used) –
10 Up command (Always set with the Down command) 6-55
11 Down command (Always set with the Up command) 6-55
12 FJOG command (ON: Forward run at jog frequency d1-17) 6-61
13 RJOG command (ON: Reverse run at jog frequency d1-17) 6-61
14 Fault reset (Reset when turned ON) 7-2
15 Emergency stop. (NO: Deceleration to stop in deceleration time set in C1-09 when ON.) 6-15
17 Emergency stop (NC: Deceleration to stop in deceleration time set in C1-09 when OFF) 6-15
18
Timer function input (Functions are set in b4-01 and b4-02 and the timer function outputs are set in
H2-.)
6-82
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com