User Constants
10-7
10
User Constants
Factory settings are given in the following table. These are factory settings for a 200 V Class Inverter with
0.4 kW (open loop vector control).
Table 10.1 User Constants
No. Name
Factory
Setting
Setting
A1-00 Language selection for digital operator display (JVOP-160)
0
A1-01 Constant access level 2
A1-03 Initialize 0
A1-04 Password 0
A1-05 Password setting 0
A2-01 to
A2-32
User setting constants –
b1-01 Reference source selection 1
b1-02 RUN command source selection 1
b1-03 Stopping method selection 0
b1-04 Prohibition of reverse operation 0
b1-07 Operation selection after switching to remote mode 0
b1-08 Run command selection in programming modes 0
b1-11 RUN delay 0 s
b1-12 HAND Fref Source 0
b2-01 Zero speed level (DC injection braking starting frequency) 0.5 Hz
b2-02 DC injection braking current 50 %
b2-03 DC injection braking time at start 0.00 s
b2-04 DC injection braking time at stop 0.50 s
b2-09 Motor pre-heat current 0%
b3-01 Speed search selection
2
b3-02 Speed search operating current
120 %
*1
b3-03 Speed search deceleration time 2.0 s
b3-05 Speed search wait time 0.2 s
b3-14 Bi-directional speed search selection 1
b4-01 Timer function ON-delay time 0.0 s
b4-02 Timer function OFF-delay time 0.0 s
b5-01 PI control mode selection 0
b5-02 Proportional gain (P) 1.00
b5-03 Integral (I) time 1.0 s
b5-04 Integral (I) limit 100.0 %
b5-06 PI limit 100.0 %
b5-07 PI offset adjustment 0.0 %
b5-08 PI delay time constant 0.00 s
b5-09 PI output characteristics selection 0
b5-10 PI output gain 1.0
b5-11 PI reverse output selection 0
b5-12 Selection of PI feedback loss detection 0
b5-13 PI feedback loss detection level 0 %
b5-14 PI feedback loss detection time 1.0 s
b5-15 PI sleep function operation level 0.0 Hz
b5-16 PI sleep operation delay time 0.0 s
b5-17 Acceleration/deceleration time for PI reference 0.0 s