5-34
Stall Prevention: L3
Con-
stant
Number
Name Description
Setting
Range
Factory
Setting
Change
during
Opera-
tion
Access
Level
MEMO-
BUS
Register
Page
L3-01
Stall prevention
selection during
accel
0: Disabled (Acceleration as set.
With a heavy load, the motor
may stall.)
1: Enabled (Acceleration stopped
when L3-02 level is exceeded.
Acceleration starts again when
the current has fallen below the
stall prevention level).
2: Intelligent acceleration mode
(Using the L3-02 level as a
basis, acceleration is
automatically adjusted. Set
acceleration time is
disregarded.)
0 to 2 1 No A 48FH 6-18
L3-02
Stall prevention
level during accel
Effective when L3-01 is set to 1 or
2.
Set as a percentage of Inverter rated
current.
Usually changing this setting is not
necessary. Reduce the setting when
the motor stalls.
0 to 200 120% No A 490H 6-18
L3-04
Stall prevention
selection during
decel
0: Disabled (Deceleration as set. If
deceleration time is too short, a
DC-Bus overvoltage may
result.)
1: Enabled (Deceleration is
stopped when the DC-Bus
voltage exceeds the stall preven-
tion level. Deceleration restarts
when the voltage falls below the
stall prevention level again.)
2: Intelligent deceleration mode
(Deceleration rate is
automatically adjusted so that in
Inverter can decelerate in the
shortest possible time. The set
deceleration time is
disregarded.)
When a braking option (Braking
Resistor Unit, Braking Unit) is
used, always set to 0.
0 to 2 1 No Q 492H 6-20
L3-05
Stall prevention
selection during
running
0: Disabled (Runs as set. With a
heavy load, the motor may stall.)
1: Deceleration using deceleration
time 1 (C1-02.)
2: Deceleration using decelera-
tiontime 2 (C1-04.)
0 to 2 1 No A 493H 6-30
L3-06
Stall prevention
level during run-
ning
Effective when L3-05 is 1 or 2.
Set as a percentage of the Inverter
rated current.
Usually changing this setting is not
necessary.
Reduce the setting when the motor
stalls.
30 to
200
120% No A 494H 6-30
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com

Table of Contents

Other manuals for YASKAWA Varispeed E7

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the YASKAWA Varispeed E7 and is the answer not in the manual?

YASKAWA Varispeed E7 Specifications

General IconGeneral
BrandYASKAWA
ModelVarispeed E7
CategoryDC Drives
LanguageEnglish

Related product manuals