Acceleration and Deceleration Characteristics
6-21
Setting Precautions
The stall prevention level during deceleration differs depending on the inverter rated voltage and input
voltage. Refer to the following table for details.
When using the braking option, be sure to set constant L3-04 to 0.
Inverter Rated/Input Voltage Stall Prevention Level during Deceleration (V)
200 V class 380
400 V class
E1-01 400 V 760
E1-01 < 400 V 660