Acceleration and Deceleration Characteristics
6-21
Setting Precautions
• The stall prevention level during deceleration differs depending on the inverter rated voltage and input
voltage. Refer to the following table for details.
• When using the braking option, be sure to set constant L3-04 to 0.
Inverter Rated/Input Voltage Stall Prevention Level during Deceleration (V)
200 V class 380
400 V class
E1-01 ≥ 400 V 760
E1-01 < 400 V 660