User Constant Tables
5-
17
b5-06
PID upper
limit
Sets the upper limit after PID-
control as a percentage of the
maximum output frequency.
0.0 to
100.0
100.0% Yes A A A A A 1AAH
6-109
PID Limit
b5-07
PID offset
adjustment
Sets the offset after PID-con-
trol as a percentage of the
maximum output frequency.
-100.0
to
+100.0
0.0% Yes A A A A A 1ABH
6-109
PID Offset
b5-08
PID first
order lag time
constant
Sets the time constant for low
pass filter for PID-control
outputs in 1-second units.
Not usually necessary to set.
0.00 to
10.00
0.00 s Yes A A A A A 1ACH
6-109
PID Delay
Time
b5-09
PID output
characteris-
tics selection
Select forward/reverse for
PID output.
0: PID output is forward.
1: PID output is reverse
(highlights the output
code)
0 or 1 0 No A A A A A 1ADH
6-109
Output Level
Sel
b5-10
PID output
gain
Sets output gain.
0.0 to
25.0
1.0 NoAAAAA1AEH
6-109
Output Gain
b5-11
PID reverse
output selec-
tion
0: 0 limit when PID output is
negative.
1: Reverses when PID output
is negative.
0 limit when reverse prohibit
is selected using b1-04.
0 or 1 0 No A A A A A 1AFH
6-109
Output Rev
Sel
b5-12
Selection of
PID feed-
back com-
mand loss
detection
0: No detection of loss of
PID feedback.
1: Detection of loss of PID
feedback.
Operation continues
during detection, with the
malfunctioning contact
not operating.
2: Detection of loss of PID
feedback.
Coasts to stop during
detection, and fault
contact operates.
0 to 2 0 No A A A A A 1B0H
6-110
Fb los Det Sel
b5-13
PID feed-
back com-
mand loss
detection
level
Sets the PID feedback loss
detection level as a percent
units, with the maximum out-
put frequency at 100%.
0 to
100
0% No A A A A A 1B1H
6-110
Fb los Det
Lvl
b5-14
PID feed-
back com-
mand loss
detection
time
Sets the PID feedback loss
detection level in s units.
0.0 to
25.5
1.0 s No A A A A A 1B2H
6-110
Fb los Det
Time
Con-
stant
Number
Name
Description
Setting
Range
Factory
Setting
Change
during
Opera-
tion
Control Methods
MEMO-
BUS
Regis-
ter
Page
Display
V/f
V/f
with
PG
Open
Loop
Vec-
tor
1
Flux
Vec-
tor
Open
Loop
Vec-
tor
2
TOE-S616-60.1.book 17 ージ 017年8月4日 金曜日 午後3時41

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the YASKAWA Varispeed G7 Series and is the answer not in the manual?

YASKAWA Varispeed G7 Series Specifications

General IconGeneral
BrandYASKAWA
ModelVarispeed G7 Series
CategoryInverter
LanguageEnglish

Related product manuals