T: Motor Autotuning
The following settings are made with the motor autotuning constants (T constants): Settings for autotuning.
T constants are displayed when autotuning mode is selected with the Digital Operator.
* 1. Set T1-02 and T1-04 when 2 is set for T1-01. Only set value 2 (2 or 3 for Control Boards ETC618046-S1033 and later) is possible for V/f control or V/
f control with PG.
* 2. These are values for a 200 V Class Inverter. Values for a 400 V Class Inverter are double.
* 3. The factory setting depends on the Inverter capacity. The value for a 200 V Class Inverter for 0.4 kW is given.
* 4. The setting range is from 10% to 200% of the Inverter rated output current. The value for a 200 V Class Inverter for 0.4 kW is given.
* 5. Applicable for Control Boards ETC618046-S1033 and later. Refer to Chapter 8 Procedure for Adjusting Constants after Replacement of Control Board
(Page 8-4) for the details of setting 3 (Shipping adjustment).
* 6. When the control method is changed, the factory setting will change. The open-loop vector 1 control factory setting is given.
* 7. Applicable for G7-Series Inverters with software versions PRG 1039 and later.
* 8. The setting range depends on the Inverter capacity. The value for a 200 V Class Inverter of 0.4 kW is given. The upper limit depends on the setting of E2-01.
Con-
stant
Number
Name
Description
Setting
Range
Factory
Setting
Change
during
Opera-
tion
Control Methods
MEMO-
BUS
Regis-
ter
Page
Display
V/f
V/f
with
PG
Open
Loop
Vec-
tor
1
Flux
Vec-
tor
Open
Loop
Vec-
tor
2
T1-00
Motor 1/2
selection
Set the location where the
autotuned motor constants are
to be stored.
1: Motor 1
2: Motor 2
1 or 2 1 No Yes Yes Yes Yes Yes 700H 4-25
Select Motor
T1-01
Autotuning
mode selec-
tion
Set the autotuning mode.
0: Rotational autotuning
1: Stationary autotuning 1
2: Stationary autotuning for
line-to-line resistance only
3: Shipping adjustment
*5
4: Stationary autotuning 2
*7
0 to 4
*1
0
*6
No Yes Yes Yes Yes Yes 701H
4-10
4-25
Tuning Mode
Sel
T1-02
Motor output
power
Set the output power of the
motor in kilowatts.
0.00 to
650.00
0.40
kW
*3
No Yes Yes Yes Yes Yes 702H 4-25
Mtr Rated
Power
T1-03
Motor rated
voltage
Set the rated voltage of the
motor in volts.
0.0 to
255.5
*2
200.0 V
*2
No No No Yes Yes Yes 703H 4-25
Rated Voltage
T1-04
Motor rated
current
Set the rated current of the
motor in amps.
0.32 to
6.40
*4
1.90 A
*3
No Yes Yes Yes Yes Yes 704H 4-25
Rated Current
T1-05
Motor base
frequency
Set the base frequency of the
motor in hertz.
0.0 to
400.0
60.0 Hz No No No Yes Yes Yes 705H 4-25
Rated Fre-
quency
T1-06
Number of
motor poles
Set the number of motor
poles.
2 to 48
poles
4 poles No No No Yes Yes Yes 706H 4-25
Number of
Poles
T1-07
Motor base
speed
Set the base speed of the
motor in min
1
.
0 to
24000
1750
min
1
No No No Yes Yes Yes 707H 4-26
Rated Speed
T1-08
Number of
PG pulses
when turning
Set the number of pulses per
revolution for the PG being
used (pulse generator or
encoder) without any multi-
plication factor.
0 to
60000
600 No No Yes No Yes No 708H 4-26
PG Pulses/
Rev
T1-09
*7
Motor no-
load current
Set the current value recorded
in the motors test results for
a motor without a load.
Displayed only when Station-
ary autotuning 2 is selected
(T1-01 = 4).
0.00 to
1.89
*8
1.20A
*3
No No No Yes Yes Yes 709H 4-26
No-Load
Current
TOE-S616-60.1.book 78 ージ 017年8月4日 金曜日 午後3時41

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the YASKAWA Varispeed G7 Series and is the answer not in the manual?

YASKAWA Varispeed G7 Series Specifications

General IconGeneral
BrandYASKAWA
ModelVarispeed G7 Series
CategoryInverter
LanguageEnglish

Related product manuals