Individual Functions
6-
147
Zero-servo Function
The zero-servo function holds the motor when the motor is stopped in what is call a zero-servo status. This
function can be used to stop the motor even with an external force acts on the motor or the analog reference
input is offset.
The zero-servo function is enabled when one of the multi-function inputs (H1-01 to H1-10) is set to 72 (zero-
servo command). If the zero-servo command is ON when the frequency (speed) reference falls below the zero-
speed level, a zero-servo status is implemented.
Related Constants
Con-
stant
Number
Name
Description
Setting
Range
Factory
Setting
Change
during
Opera-
tion
Control Methods
MEMO
BUS
Regis-
ter
Display
V/f
V/f
with
PG
Open
Loop
Vector
1
Flux
Vec-
tor
Open
Loop
Vector
2
b2-01
Zero-speed
level (DC injec-
tion braking
starting fre-
quency)
Used to set the frequency which
starts DC injection braking in
units of Hz when deceleration to
stop is selected.
When b2-01 is less than E1-09,
E1-09 becomes the DC injection
braking starting frequency.
(For flux vector control, zero-
speed control from B2-01)
0.0 to
10.0
0.5 Hz No A A A A A 189H
DCInj Start
Freq
b9-01
Zero-servo gain Adjust the strength of the zero-
servo lock.
Enabled when the zero-servo
command is set for a multi-func-
tion input. When the zero-servo
command has been input and the
frequency reference drop below
excitation level (b2-01), a posi-
tion control loop is created and
the motor stops. Increasing the
zero-servo gain in turn increases
the strength of the lock. Increas-
ing it by too much will cause
oscillation.
0 to
100
5 No No No No A No 1DAH
Zero Servo
Gain
b9-02
Zero-servo
completion
width
Sets the output width of the P-
lock completion signal.
Enabled when the “zero-servo
completion (end)” is set for a
multi-function input. The zero-
servo completion signal is ON
when the current position is
within the range (the zero-servo
position + zero-servo completion
width.)
Set the allowable position dis-
placement from the zero-servo
position to 4 times the pulse rate
of the PG (pulse generator,
encoder) in use.
0 to
16383
10 No No No No A No 1DBH
Zero Servo
Count
TOE-S616-60.1.book 147 ページ 017年8月4日 金曜日 午後3時41分

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the YASKAWA Varispeed G7 Series and is the answer not in the manual?

YASKAWA Varispeed G7 Series Specifications

General IconGeneral
BrandYASKAWA
ModelVarispeed G7 Series
CategoryInverter
LanguageEnglish

Related product manuals