Individual Functions
6-
117
Energy-saving
To perform energy saving, set b8-01 (Energy Saving Mode Selection) to 1. Energy-saving control can be per-
formed using both V/f control and vector control. The constants to be adjusted are different for each. In V/f
control, adjust b8-04 to b8-06, and in vector control, adjust b8-02 and b8-03.
Related Constants
* 1. The factory setting is 1.0 when using flux vector control.
* 2. The factory setting is 2.00 s when Inverter capacity is 55 kW min.
The factory setting will change when the control method is changed. The open-loop vector 1 factory setting is given.
* 3. By setting E2-11 (Motor rated output) the appropriate value will be set.
* 4. The factory settings depend on the Inverter capacity. The values for a 200 V Class Inverter of 0.4 kW are given.
Con-
stant
Number
Name
Description
Setting
Range
Factory
Setting
Change
during
Opera-
tion
Control Methods
MEMO
BUS
Regis-
ter
Display
V/f
V/f
with
PG
Open
Loop
Vector
1
Flux
Vec-
tor
Open
Loop
Vector
2
b8-01
Energy-saving
mode selection
Select whether to enable or dis-
able energy-saving control.
0: Disable
1: Enable
0 or 1 0 No A A A A A 1CCH
Energy Save
Sel
b8-02
Energy-saving
gain
Set the energy-saving gain with
the open-loop vector control
method.
0.0 to
10.0
0.7
*1
YesNoNoAAA1CDH
Energy Save
Gain
b8-03
Energy-saving
filter time con-
stant
Set the energy-saving filter time
constant with the open-loop vec-
tor control method.
0.00 to
10.0
0.50 s
*2
YesNoNoAAA1CEH
Energy Save
F.T
b8-04
Energy-saving
coefficient
Set the maximum motor effi-
ciency value.
Set the motor rated capacity in
E2-11, and adjust the value by 5%
at a time until output power
reaches a minimum value.
0.0 to
655.00
288.20
*3 *4
No A A No No No 1CFH
Energy Save
COEF
b8-05
Power detection
filter time con-
stant
Set the time constant for output
power detection.
0 to
2000
20 ms No A A No No No 1D0H
kW Filter Time
b8-06
Search opera-
tion voltage
limiter
Set the limit value of the voltage
control range during search opera-
tion.
Perform search operation to opti-
mize operations using minute
variations in voltage using
energy-saving control. Set to 0 to
disable the search operation.
100% is the motor base voltage.
0 to
100
0% No A A No No No 1D1H
Search V Limit
E2-02
Motor rated slip Sets the motor rated slip in Hz
units.
These set values will become the
reference values for slip compen-
sation.
This constant is automatically set
during autotuning.
0.00 to
20.00
2.90
Hz
*4
NoAAAAA30FH
Motor Rated
Slip
E2-11
Motor rated
output
Set the rated output of the motor
in units of 0.01 kW.
This constant is automatically set
during autotuning.
0.00 to
650.00
0.40
*4
NoQQQQQ318H
Mtr Rated
Power
TOE-S616-60.1.book 117 ページ 017年8月4日 金曜日 午後3時41分

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the YASKAWA Varispeed G7 Series and is the answer not in the manual?

YASKAWA Varispeed G7 Series Specifications

General IconGeneral
BrandYASKAWA
ModelVarispeed G7 Series
CategoryInverter
LanguageEnglish

Related product manuals