User Constant Tables
5-
97
Carrier Frequency Constant Settings that Change with the Inverter
Capacity (o2-04) and Control Method (A1-02) (Applicable for PRG 1042
and Later)
200 V Class Inverters
Con-
stant
Num-
ber
Name Unit Factory Setting
– Inverter Capacity kW 0.4 0.75 1.5 2.2 3.7 5.5 7.5 11 15
o2-04 kVA Selection 1012345678
C6-02
*1
Carrier
frequency
selection
V/f
Factory setting –6
66666666
Maximum
setting
–666666666
V/f with
PG
Factory setting –666666666
Maximum
setting
–666666666
Open-
loop
vector
Factory setting –666666666
Maximum
setting
–666666666
Flux
vector
Factory setting –111111111
Maximum
setting
–666666666
C6-03
(C6-04)
*2
Carrier
frequency
upper limit
(carrier
frequency
lower limit)
V/f
Factory setting kHz 15.0 15.0 15.0 15.0 15.0 15.0 15.0 15.0 15.0
Setting range kHz
0.4 to
15.0
0.4 to
15.0
0.4 to
15.0
0.4 to
15.0
0.4 to
15.0
0.4 to
15.0
0.4 to
15.0
0.4 to
15.0
0.4 to
15.0
V/f with
PG
Factory setting kHz 15.0 15.0 15.0 15.0 15.0 15.0 15.0 15.0 15.0
Setting range kHz
0.4 to
15.0
0.4 to
15.0
0.4 to
15.0
0.4 to
15.0
0.4 to
15.0
0.4 to
15.0
0.4 to
15.0
0.4 to
15.0
0.4 to
15.0
Open-
loop
vector
Factory setting kHz 15.0 15.0 15.0 15.0 15.0 15.0 15.0 15.0 15.0
Setting range kHz
2.0 to
15.0
2.0 to
15.0
2.0 to
15.0
2.0 to
15.0
2.0 to
15.0
2.0 to
15.0
2.0 to
15.0
2.0 to
15.0
2.0 to
15.0
Flux
vector
Factory setting kHz 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0
Setting range kHz
2.0 to
15.0
2.0 to
15.0
2.0 to
15.0
2.0 to
15.0
2.0 to
15.0
2.0 to
15.0
2.0 to
15.0
2.0 to
15.0
2.0 to
15.0