5
-40
F: Option Constants
The following settings are made with the option constants (F constants): Settings for option boards
PG Option Setup: F1
User constants for the PG Speed Control Board are shown in the following table.
Con-
stant
Number
Name
Description
Setting
Range
Factory
Setting
Change
during
Opera-
tion
Control Methods
MEMO-
BUS
Regis-
ter
Page
Display
V/f
V/f
with
PG
Open
Loop
Vec-
tor
1
Flux
Vec-
tor
Open
Loop
Vec-
tor
2
F1-01
PG constant Sets the number of PG (pulse
generator or encoder) pulses.
Sets the number of pulses per
motor revolution.
0 to
60000
600 No No Q No Q No 380H
6-160
PG Pulses/
Rev
F1-02
Operation
selection at
PG open cir-
cuit (PGO)
Sets the PG disconnection
stopping method.
0: Ramp to stop
(Deceleration stop using
Deceleration Time 1, C1-
02.)
1: Coast to stop
2: Fast stop (Emergency stop
using the deceleration
time in C1-09.)
3: Continue operation (To
protect the motor or
machinery, do not
normally make this
setting.)
0 to 3 1 No No A No A No 381H
6-160
PG Fdbk
Loss Sel
F1-03
Operation
selection at
overspeed
(OS)
Sets the stopping method
when an overspeed (OS) fault
occurs.
0: Ramp to stop
(Deceleration stop using
Deceleration Time 1, C1-
02.)
1: Coast to stop
2: Fast stop (Emergency stop
using the deceleration
time in C1-09.)
3: Continue operation (To
protect the motor or
machinery, do not
normally make this
setting.)
0 to 3 1 No No A No A A 382H
6-160
PG Over-
speed Sel
F1-04
Operation
selection at
deviation
Sets the stopping method
when a speed deviation
(DEV) fault occurs.
0: Ramp to stop
(Deceleration stop using
Deceleration Time 1, C1-
02.)
1: Coast to stop
2: Fast stop (Emergency stop
using the deceleration
time in C1-09.)
3: Continue operation (DEV
is displayed and operation
continued.)
0 to 3 3 No No A No A A 383H
6-160
PG Devia-
tion Sel
TOE-S616-60.1.book 40 ージ 017年8月4日 金曜日 午後3時41

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the YASKAWA Varispeed G7 Series and is the answer not in the manual?

YASKAWA Varispeed G7 Series Specifications

General IconGeneral
BrandYASKAWA
ModelVarispeed G7 Series
CategoryInverter
LanguageEnglish

Related product manuals