EasyManuals Logo

YASKAWA Varispeed G7 Series User Manual

YASKAWA Varispeed G7 Series
541 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #127 background imageLoading...
Page #127 background image
Adjustment Suggestions
4-
29
Adjustment Suggestions
If hunting, vibration, or other problems originating in the control system occur during trial operation,
adjust the constants listed in the following table according to the control method. This table lists only the
most commonly used user constants.
Table 4.3 Adjusted User Constants
Control
Method
Name (Constant
Number)
Performance
Factory
Setting
Recom-
mended
Setting
Adjustment Method
V/f control
(A1-02 = 0
or 1)
Hunting-prevention
gain (N1-02)
Controlling hunting
and vibration in mid-
dle-range speeds (10 to
40 Hz)
1.00 0.50 to 2.00
Reduce the setting if
torque is insufficient for
heavy loads.
Increase the setting if hunt-
ing or vibration occurs for
light loads.
Carrier frequency
selection
(C6-02)
Reducing motor
magnetic noise
Controlling hunting
and vibration at low
speeds
Depends
on capac-
ity
0 to
default
Increase the setting if
motor magnetic noise is
high.
Reduce the setting if hunt-
ing or vibration occurs at
low to middle-range
speeds.
Torque compensation
primary delay time
constant (C4-02)
Increasing torque
and speed response
Controlling hunting
and vibration
Depends
on capac-
ity
200 to 1000
ms
Reduce the setting if
torque or speed response is
slow.
Increase the setting if hunt-
ing or vibration occurs.
Torque compensation
gain (C4-01)
Improving torque at
low speeds (10 Hz
or lower)
Controlling hunting
and vibration
1.00 0.50 to 1.50
Increase the setting if
torque is insufficient at
low speeds.
Reduce the setting if hunt-
ing or vibration occurs for
light loads.
Middle output
frequency voltage
(E1-08)
Minimum output
frequency voltage
(E1-10)
Improving torque at
low speeds
Controlling shock at
startup
Depends
on capac-
ity and
voltage
Default to
Default + 3
to 5 V
*
Increase the setting if
torque is insufficient at
low speeds.
Reduce the setting if shock
at startup is large.
Open-loop
vector 1
control
(A1-02 = 2)
Speed feedback
detection control
(AFR) gain
(N2-01)
Increasing torque
and speed response
Controlling hunting
and vibration in mid-
dle-range speeds (10
to 40 Hz)
1.00 0.50 to 2.00
Reduce the setting if
torque or speed response is
slow.
Increase the setting if hunt-
ing or vibration occurs.
Torque compensation
primary delay time
constant (C4-02)
Increasing torque
and speed response
Controlling hunting
and vibration
20 ms
20 to
100 ms
Reduce the setting if
torque or speed response is
slow.
Increase the setting if hunt-
ing or vibration occurs.
Slip compensation
primary delay time
(C3-02)
Increasing speed
response
Improving speed sta-
bility
200 ms
100 to
500 ms
Reduce the setting if speed
response is slow.
Increase the setting if the
speed is not stable.
Slip compensation
gain (C3-01)
Improving speed accu-
racy
1.0 0.5 to 1.5
Increase the setting if
speed response is slow.
Reduce the setting if the
speed is too fast.
TOE-S616-60.1.book 29 ージ 017年8月4日 金曜日 午後3時41

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the YASKAWA Varispeed G7 Series and is the answer not in the manual?

YASKAWA Varispeed G7 Series Specifications

General IconGeneral
BrandYASKAWA
ModelVarispeed G7 Series
CategoryInverter
LanguageEnglish

Related product manuals