d: Reference Constants
The following settings are made with the reference constants (d constants): Frequency references.
Preset Reference: d1
User constants for frequency references are shown in the following table.
Con-
stant
Number
Name
Description
Setting
Range
Factory
Setting
Change
during
Opera-
tion
Control Methods
MEMO-
BUS
Regis-
ter
Page
Display
V/f
V/f
with
PG
Open
Loop
Vec-
tor
1
Flux
Vec-
tor
Open
Loop
Vec-
tor
2
d1-01
Frequency
reference 1
Sets the frequency reference
in the units used in o1-03.
0 to
400.00
*
0.00 Hz Yes Q Q Q Q Q 280H
4-8
6-5
Reference 1
d1-02
Frequency
reference 2
The frequency reference
when multi-step speed refer-
ence 1 is ON for a multi-func-
tion input.
0.00 Hz Yes Q Q Q Q Q 281H
4-8
6-5
Reference 2
d1-03
Frequency
reference 3
The frequency reference
when multi-step speed refer-
ence 2 is ON for a multi-func-
tion input.
0.00 Hz Yes Q Q Q Q Q 282H
4-8
6-5
Reference 3
d1-04
Frequency
reference 4
The frequency reference
when multi-step speed refer-
ences 1 and 2 are ON for
multi-function inputs.
0.00 Hz Yes Q Q Q Q Q 283H
4-8
6-5
Reference 4
d1-05
Frequency
reference 5
The frequency when multi-
step speed reference 3 is ON
for a multi-function input.
0.00 Hz Yes A A A A A 284H 6-5
Reference 5
d1-06
Frequency
reference 6
The frequency reference
when multi-step speed refer-
ences 1 and 3 are ON for
multi-function inputs.
0.00 Hz Yes A A A A A 285H 6-5
Reference 6
d1-07
Frequency
reference 7
The frequency reference
when multi-step speed refer-
ences 2 and 3 are ON for
multi-function inputs.
0.00 Hz Yes A A A A A 286H 6-5
Reference 7
d1-08
Frequency
reference 8
The frequency reference
when multi-step speed refer-
ences 1, 2, and 3 are ON for
multi-function inputs.
0.00 Hz Yes A A A A A 287H 6-5
Reference 8
d1-09
Frequency
reference 9
The frequency reference
when multi-step speed refer-
ence 4 is ON for a multi-func-
tion input.
0.00 Hz Yes A A A A A 288H
Reference 9
d1-10
Frequency
reference 10
The frequency reference
when multi-step speed refer-
ences 1 and 4 are ON for
multi-function inputs.
0.00 Hz Yes A A A A A 28BH
Reference 10
d1-11
Frequency
reference 11
The frequency reference
when multi-step speed refer-
ences 2 and 4 are ON for a
multi-function inputs.
0.00 Hz Yes A A A A A 28CH
Reference 11
TOE-S616-60.1.book 28 ージ 017年8月4日 金曜日 午後3時41

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the YASKAWA Varispeed G7 Series and is the answer not in the manual?

YASKAWA Varispeed G7 Series Specifications

General IconGeneral
BrandYASKAWA
ModelVarispeed G7 Series
CategoryInverter
LanguageEnglish

Related product manuals