5
-96
Note Attach a Momentary Power Interruption Compensation Unit if compensation for power interruptions of up to 2.0 seconds is required for 400 V Class Inverters
with outputs of 0.4 to 7.5 kW.
* 1. The initial settings for C6-02 are as follows: 1: 2.0 kHz, 2: 5.0 kHz, 3: 8.0 kHz, 4: 10.0 kHz, 5: 12.5 kHz, 6: 15.0 kHz, and F: user setting (initial value for Invert-
ers of 90 or 110 kW: 3.0 kHz).
* 2. This setting is for software versions PRG 1039 and earlier.
The carrier frequencies for the settings of C6-11 are as follows:
1: 2.0 kHz, 2: 4.0 kHz, 3: 6.0 kHz, 4: 8.0 kHz.
Con-
stant
Number
Name Unit Factory Setting
Inverter Capacity
kW 18.5 22 30 37 45 55 75 90 110 132 160 185 220 300
E2-11
Motor Rated
Capacity
E4-07
2nd Motor Rated
Capacity
o2-04 kVA selection 2A 2B 2C 2D 2E 2F 30 31 32 33 34 35 36 37
b8-03
Energy-saving filter
time constant
s 0.50 (Open-loop vector control) 2.00 (Open-loop vector control)
b8-04
Energy-saving coeffi-
cient
115.74 103.58
92.54 76.32 71.56 67.20 46.20 38.91 36.23 32.79 30.13 30.57 27.13 21.76
C6-02
Carrier frequency
selection
*1
3333322FF11
1
*1
1
*1
1
C6-11
Carrier frequency
selection for open-
loop vector 2 control
*2
4444422111111 1
Carrier frequency
selection upper limit
3333322
3
*1
3
*1
1111 1
E2-01
(E4-01)
Motor rated current A 32.9 38.6 52.3 65.6 79.7 95.0
130.0 156.0 190.0 223.0 270.0 310.0 370.0 500.0
E2-02
(E4-02)
Motor rated slip Hz 1.67 1.70 1.80 1.33 1.60 1.46 1.39 1.40 1.40 1.38 1.35 1.30 1.30 1.25
E2-03
(E4-03)
Motor no-load current A 7.8 9.2 10.9 19.1 22.0 24.0 36.0 40.0 49.0 58.0 70.0 81.0 96.0 130.0
E2-05
(E4-05)
Motor line-to-line
resistance
Ω
0.403 0.316 0.269 0.155 0.122 0.088 0.092 0.056 0.046 0.035 0.029 0.025 0.020 0.014
E2-06
(E4-06)
Motor leak inductance % 20.1 23.5 20.7 18.8 19.9 20.0 20.0 20.0 20.0 20.0 20.0 20.0 20.0 20.0
E2-10
Motor iron loss for
torque compensation
W 508 586 750 925 1125 1260 1600 1760 2150 2350 2850 3200 3700 4700
L2-02
Momentary power
loss ridethru time
s 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0
L2-03
Min. baseblock (BB)
time
s 1.0 1.1 1.1 1.2 1.2 1.3 1.5 1.7 1.7 1.8 1.9 2.0 2.1 2.1
L2-04 Voltage recovery time s 0.6 0.6 0.6 0.6 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0
L8-02
Overheat pre-alarm
level
°C 95 95 95 95 95 100 105 105 120 110 115 100 110 115
L8-39
Reduced carrier
frequency
kHz 2.0 2.0 2.0 2.0 2.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0
N1-03
Hunting-prevention
time constant
ms 10 10 10 10 10 30 30 30 30 30 30 100 100 100
N5-02
Motor acceleration
time
s
0.317 0.355 0.323 0.320 0.387 0.317 0.533 0.592 0.646 0.673 0.777 0.864 0.910 1.392
TOE-S616-60.1.book 96 ージ 017年8月4日 金曜日 午後3時41

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the YASKAWA Varispeed G7 Series and is the answer not in the manual?

YASKAWA Varispeed G7 Series Specifications

General IconGeneral
BrandYASKAWA
ModelVarispeed G7 Series
CategoryInverter
LanguageEnglish

Related product manuals