5
-98
* 1. The carrier frequency is as follows depending on the C6-02 setting.
1: 2.0 kHz, 2: 5.0 kHz, 3: 8.0 kHz, 4: 10.0 kHz, 5: 12.5 kHz, 6: 15.0 kHz, F: User setting (initial value for 400 V, 90 kW and 110 kW: 3.0 kHz)
* 2. C6-04 (Carrier Frequency Lower Limit) can be set only in V/f control and V/f control with PG modes.
Con-
stant
Num-
ber
Name Unit Factory Setting
– Inverter Capacity kW 18.5 22 30 37 45 55 75 90 110
o2-04 kVA Selection 1 9 A B C D E F 10 11
C6-02
*1
Carrier
frequency
selection
V/f
Factory setting –6
44444411
Maximum
setting
–664444411
V/f with
PG
Factory setting –644444411
Maximum
setting
–664444411
Open-
loop
vector
Factory setting –644444411
Maximum
setting
–664444411
Flux
vector
Factory setting –111111111
Maximum
setting
–664444411
C6-03
(C6-04)
*2
Carrier
frequency
upper limit
(carrier
frequency
lower limit)
V/f
Factory setting kHz 15.0 10.0 10.0 10.0 10.0 10.0 10.0 2.0 2.0
Setting range kHz
0.4 to
15.0
0.4 to
15.0
0.4 to
10.0
0.4 to
10.0
0.4 to
10.0
0.4 to
10.0
0.4 to
10.0
0.4 to
2.0
0.4 to
2.0
V/f with
PG
Factory setting kHz 15.0 10.0 10.0 10.0 10.0 10.0 10.0 2.0 2.0
Setting range kHz
0.4 to
15.0
0.4 to
15.0
0.4 to
10.0
0.4 to
10.0
0.4 to
10.0
0.4 to
10.0
0.4 to
10.0
0.4 to
2.0
0.4 to
2.0
Open-
loop
vector
Factory setting kHz 15.0 10.0 10.0 10.0 10.0 10.0 10.0 2.0 2.0
Setting range kHz
2.0 to
15.0
2.0 to
15.0
2.0 to
10.0
2.0 to
10.0
2.0 to
10.0
2.0 to
10.0
2.0 to
10.0
2.0 to
2.0
2.0 to
2.0
Flux
vector
Factory setting kHz 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0
Setting range kHz
2.0 to
15.0
2.0 to
15.0
2.0 to
10.0
2.0 to
10.0
2.0 to
10.0
2.0 to
10.0
2.0 to
10.0
2.0 to
2.0
2.0 to
2.0
TOE-S616-60.1.book 98 ページ 2017年8月4日 金曜日 午後3時41分