6
-148
Multi-function Contact Input Functions (H1-01 to H1-10)
Multi-function Contact Output Functions (H2-01 to H2-05)
To output the zero-servo status externally, assign the Zero-servo End signal (setting 33) to one of the multi-
function outputs (H2-01 to H2-05).
Monitor Function
Time Chart
A time chart for the zero-servo function is given in Time Chart for Zero-servo.
Fig 6.83 Time Chart for Zero-servo
Set-
ting
Value
Function
Control Methods
V/f
V/f
with
PG
Open
Loop
Vec-
tor
1
Flux
Vec-
tor
Open
Loop
Vec-
tor
2
72 Zero-servo command (ON: Zero-servo) No No No Yes No
Set-
ting
Value
Function
Control Methods
V/f
V/f
with
PG
Open
Loop
Vec-
tor
1
Flux
Vec-
tor
Open
Loop
Vec-
tor
2
33
Zero-servo end
ON: Current position is within zero-servo start position ± the zero-servo end width.
No No No Yes No
Con-
stant
Number
Name
Description
Output Signal
Level During
Multi-Function
Analog Output
Min.
Unit
Control Methods
MEMO
BUS
Reg-
ister
Display
V/f
V/f
with
PG
Open
Loop
Vector
1
Flux
Vec-
tor
Open
Loop
Vector
2
U1-35
Zero-servo
movement
pulses
Shows the number of PG pulses
times 4 for the movement range
when stopped at zero.
(Cannot be out-
put.)
1 No No No A No 62H
Zero Servo
Pulse
Run Command
ON OFF
Zero servo command
Frequency (speed) reference
Excitation level
b2-01
Motor speed
Zero Servo End signal Zero-servo status
ON OFF
TOE-S616-60.1.book 148 ページ 017年8月4日 金曜日 午後3時41分

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the YASKAWA Varispeed G7 Series and is the answer not in the manual?

YASKAWA Varispeed G7 Series Specifications

General IconGeneral
BrandYASKAWA
ModelVarispeed G7 Series
CategoryInverter
LanguageEnglish

Related product manuals