EasyManuals Logo

YASKAWA Varispeed G7 Series User Manual

YASKAWA Varispeed G7 Series
541 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #379 background imageLoading...
Page #379 background image
6
-146
Related Constants
Setting Precautions
Droop control is disabled if b7-01 is set to 0.0.
Set b7-01 to the amount of slip as the percentage of slip when the maximum output frequency is input and
the rated torque is generated.
Constant b7-02 is used to adjust the responsiveness of droop control. Increase this setting if oscillation or
hunting occur.
Disable the feed forward control (N5-01 = 0) when using the droop control function.
Setting the Droop Control Gain
Set the droop control gain as the speed reduction at a 100% motor torque, as a percentage of the maximum
output frequency.
Fig 6.82 Droop Control Gain
Con-
stant
Number
Name
Description
Setting
Range
Factory
Setting
Change
during
Opera-
tion
Control Methods
MEMO
BUS
Regis-
ter
Display
V/f
V/f
with
PG
Open
Loop
Vector
1
Flux
Vec-
tor
Open
Loop
Vector
2
b7-01
Droop control
gain
Sets the slip as a percentage of
maximum frequency when the
maximum output frequency is
specified and the rated torque
occurs.
Droop-control is not performed
when the setting is 0.0.
0.0 to
100.0
0.0 Yes No No No A A 1CAH
Droop Quantity
b7-02
Droop control
delay time
Droop control responsiveness
constant
When hunting or oscillation
occurs, increase the value.
0.03 to
2.00
0.05 s No A A A A A 1CBH
Droop Delay
Time
To r que
Speed
Speed reference
0
100%
b7-01
TOE-S616-60.1.book 146 ページ 017年8月4日 金曜日 午後3時41分

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the YASKAWA Varispeed G7 Series and is the answer not in the manual?

YASKAWA Varispeed G7 Series Specifications

General IconGeneral
BrandYASKAWA
ModelVarispeed G7 Series
CategoryInverter
LanguageEnglish

Related product manuals