5
-20
Energy Saving: b8
User constants for energy-saving control functions are shown in the following table.
* 1. The factory setting is 1.0 when using flux vector control.
* 2. The factory setting is 2.00 s when Inverter capacity is 55 kW min.
The factory setting will change when the control method is changed. The open-loop vector 1 factory setting is given.
* 3. By setting E2-11 (Motor rated output) the appropriate value will be set.
* 4. The factory setting depends on the Inverter capacity. The value for a 200 V Class Inverter of 0.4 kW is given.
Con-
stant
Number
Name
Description
Setting
Range
Factory
Setting
Change
during
Opera-
tion
Control Methods
MEMO-
BUS
Regis-
ter
Page
Display
V/f
V/f
with
PG
Open
Loop
Vec-
tor
1
Flux
Vec-
tor
Open
Loop
Vec-
tor
2
b8-01
Energy-sav-
ing mode
selection
Select whether to enable or
disable energy-saving con-
trol.
0: Disable
1: Enable
0 or 1 0 No A A A A A 1CCH 6-117
Energy Save
Sel
b8-02
Energy-
saving gain
Set the energy-saving gain
with the open-loop vector
control method.
0.0 to
10.0
0.7
*1
Yes No No A A A 1CDH 6-117
Energy Save
Gain
b8-03
Energy-sav-
ing filter time
constant
Set the energy-saving filter
time constant with the open-
loop vector control method.
0.00 to
10.0
0.50 s
*2
Yes No No A A A 1 CEH 6-11 7
Energy Save
F.T
b8-04
Energy-
saving
coefficient
Set the maximum motor effi-
ciency value.
Set the motor rated capacity
in E2-11, and adjust the value
by 5% at a time until output
power reaches a minimum
value.
0.0 to
655.00
288.20
*3 *4
No A A No No No 1CFH 6-117
Energy Save
COEF
b8-05
Power detec-
tion filter
time constant
Set the time constant for out-
put power detection.
0 to
2000
20 ms No A A No No No 1D0H 6-117
kW Filter
Time
b8-06
Search opera-
tion voltage
limiter
Set the limit value of the volt-
age control range during
search operation.
Perform search operation to
optimize operations using
minute variations in voltage
using energy-saving control.
Set to 0 to disable the search
operation. 100% is the motor
base voltage.
0 to
100
0% No A A No No No 1D1H 6-117
Search V
Limit
TOE-S616-60.1.book 20 ージ 017年8月4日 金曜日 午後3時41

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the YASKAWA Varispeed G7 Series and is the answer not in the manual?

YASKAWA Varispeed G7 Series Specifications

General IconGeneral
BrandYASKAWA
ModelVarispeed G7 Series
CategoryInverter
LanguageEnglish

Related product manuals