User Constant Tables
5-
55
Multi-function Analog Outputs: H4
User constants for multi-function analog outputs are shown in the following table.
Con-
stant
Number
Name
Description
Setting
Range
Factory
Setting
Change
during
Opera-
tion
Control Methods
MEMO-
BUS
Regis-
ter
Page
Display
V/f
V/f
with
PG
Open
Loop
Vec-
tor
1
Flux
Vec-
tor
Open
Loop
Vec-
tor
2
H4-01
Monitor
selection
(terminal
FM)
Sets the number of the monitor
item to be output (U1-)
from terminal FM.
4, 10 to 14, 25, 28, 34, 39, 40
cannot be set. 29 to 31 and 41
are not used.
1 to 45
2 NoAAAAA41DH6-89
Terminal
FM Sel
1 to 99
H4-02
Gain (ter-
minal FM)
Sets the multi-function analog
output 1 voltage level gain.
Sets whether the monitor item
output will be output in multi-
ples of 10 V.
The maximum output from the
terminal is 10 V. A meter cali-
bration function is available.
*
0.00 to
2.50
1.00 Yes Q Q Q Q Q 41EH
4-8
6-89
Terminal
FM Gain
H4-03
Bias (termi-
nal FM)
Sets the multi-function analog
output 1 voltage level bias.
Sets output characteristic up/
down parallel movement as a
percentage of 10 V.
The maximum output from the
terminal is 10 V. A meter cali-
bration function is available.
*
-10.0 to
+10.0
0.0% Yes A A A A A 41FH 6-89
Terminal
FM Bias
H4-04
Monitor
selection
(terminal
AM)
Sets the number of the monitor
item to be output (U1-)
from terminal AM.
4, 10 to 14, 25, 28, 34, 39, 40
cannot be set. 29 to 31 and 41
are not used.
1 to 45
3 No A A A A A 420H 6-89
Terminal
AM Sel
1 to 99
H4-05
Gain (ter-
minal AM)
Set the voltage level gain for
multi-function analog output 2.
Set the number of multiples of
10 V to be output as the 100%
output for the monitor items.
The maximum output from the
terminal is 10 V. A meter cali-
bration function is available.
*
0.00 to
2.50
0.50 Yes Q Q Q Q Q 421H
4-8
6-89
Terminal
AM Gain
H4-06
Bias (termi-
nal AM)
Sets the multi-function analog
output 2 voltage level bias.
Sets output characteristic up/
down parallel movement as a
percentage of 10 V.
The maximum output from the
terminal is 10 V. A meter cali-
bration function is available.
*
-10.0 to
+10.0
0.0% Yes A A A A A 422H 6-89
Terminal
AM Bias
H4-07
Analog out-
put 1 signal
level selec-
tion
Sets the signal output level for
multi-function output 1 (termi-
nal FM)
0: -10 to 10 V output
1: -10 to 10 V output
0 or 1 0 No A A A A A 423H 6-90
AO Level
Select1