5
-64
Fault Restart: L5
User constants for restarting faults are shown in the following table.
L4-02
Speed agree
detection
width
Effective when “Frequency
(speed) agree 1,” “Desired fre-
quency (speed) agree 1,” or
“Frequency (FOUT) detection
1,” Frequency (FOUT) detec-
tion 2 is set for a multi-function
output.
Sets the frequency detection
width in Hz units.
0.0 to
20.0
2.0 Hz No A A A A A 49AH 6-51
Spd Agree
Width
L4-03
Speed agree
detection
level (+/-)
Effective when “Desired fre-
quency (speed) agree 2,” “Fre-
quency (FOUT) detection 3,”
or “Frequency (FOUT) detec-
tion 4" is set for a multi-func-
tion output.
Frequency that should be
detected is set in Hz units.
-400.0
to
+400.0
0.0 Hz No A A A A A 49BH 6-52
Spd Agree
Lvl+-
L4-04
Speed agree
detection
width (+/-)
Effective when “Frequency
(speed) agree 2,” “Desired fre-
quency (speed) agree 2,” Fre-
quency (FOUT) detection 3 or
“Frequency detection 4" is set
for a multi-function output.
Frequency detection width is
set in Hz units.
0.0 to
20.0
2.0 Hz No A A A A A 49CH 6-52
Spd Agree
Width+-
L4-05
Operation
when fre-
quency ref-
erence is
missing
0: Stop (Operation follows the
frequency reference.)
1: Operation at 80% speed
continues. (At 80% of speed
before the frequency
reference was lost)
Frequency reference is lost:
Frequency reference dropped
over 90% in 400 ms.
0 or 1 0 No A A A A A 49DH 6-72
Ref Loss
Sel
Con-
stant
Number
Name
Description
Setting
Range
Factory
Setting
Change
during
Opera-
tion
Control Methods
MEMO-
BUS
Regis-
ter
Page
Display
V/f
V/f
with
PG
Open
Loop
Vec-
tor
1
Flux
Vec-
tor
Open
Loop
Vec-
tor
2
L5-01
Number of
auto restart
attempts
Sets the number of auto restart
attempts.
Automatically restarts after a
fault and conducts a speed
search from the run frequency.
0 to 10 0 No A A A A A 49EH 6-73
Num of
Restarts
L5-02
Auto restart
operation
selection
Sets whether a fault contact
output is activated during fault
restart.
0: Not output (Fault contact is
not activated.)
1: Output (Fault contact is
activated.)
0 or 1 0 No A A A A A 49FH 6-73
Restart Sel
Con-
stant
Number
Name
Description
Setting
Range
Factory
Setting
Change
during
Opera-
tion
Control Methods
MEMO-
BUS
Regis-
ter
Page
Display
V/f
V/f
with
PG
Open
Loop
Vec-
tor
1
Flux
Vec-
tor
Open
Loop
Vec-
tor
2
TOE-S616-60.1.book 64 ージ 017年8月4日 金曜日 午後3時41

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the YASKAWA Varispeed G7 Series and is the answer not in the manual?

YASKAWA Varispeed G7 Series Specifications

General IconGeneral
BrandYASKAWA
ModelVarispeed G7 Series
CategoryInverter
LanguageEnglish

Related product manuals