Multi-function Selections: o2
User constants for Digital Operator key functions are shown in the following table.
Con-
stant
Number
Name
Description
Setting
Range
Factory
Setting
Change
during
Opera-
tion
Control Methods
MEMO-
BUS
Regis-
ter
Page
Display
V/f
V/f
with
PG
Open
Loop
Vec-
tor
1
Flux
Vec-
tor
Open
Loop
Vec-
tor
2
o2-01
LOCAL/
REMOTE
key enable/
disable
Sets the Digital Operator
Local/Remote Key
0: Disabled
1: Enabled (Switches
between the Digital
Operator and the constant
settings.)
0 or 1 1 No A A A A A 505H
6-150
Local/
Remote Key
o2-02
STOP key
during con-
trol circuit
terminal
operation
Sets the Stop Key in the run
mode.
0: Disabled (When the Run
Command is issued from
and external terminal, the
Stop Key is disabled.)
1: Enabled (Effective even
during run.)
0 or 1 1 No A A A A A 506H
6-151
Oper STOP
Key
o2-03
User con-
stant initial
value
Clears or stores user initial
values.
0: Stores/not set
1: Begins storing (Records
the set constants as user
initial values.)
2: All clear (Clears all
recorded user initial
values)
When the set constants are
recorded as user initial val-
ues, 1110 will be set in A1-
03.
0 to 2 0 No A A A A A 507H
6-151
User Defaults
o2-04
kVA selection
Do not set. 0 to FF
0
*1
No A A A A A 508H
Inverter
Model #
o2-05
Frequency
reference set-
ting method
selection
When the frequency reference
is set on the Digital Operator
frequency reference monitor,
sets whether the Enter Key is
necessary.
0: Enter Key needed
1: Enter Key not needed
When set to 1, the Inverter
accepts the frequency refer-
ence without Enter Key oper-
ation.
0 or 1 0 No A A A A A 509H
6-151
Operator
M.O.P.
o2-06
Operation
selection
when digital
operator is
disconnected
Sets the operation when the
Digital Operator is discon-
nected.
0: Disabled (Operation
continues even if the
Digital Operator is
disconnected.)
1: Enabled (OPR is detected
at Digital Operator
disconnection. Inverter
output is cut off, and fault
contact is operated.)
0 or 1 0 No A A A A A 50AH
Oper
Detection
o2-07
Cumulative
operation
time setting
Sets the cumulative operation
time in hour units.
Operation time is calculated
from the set values.
0 to
65535
0 hr No A A A A A 50BH
6-151
Elapsed Time
Set
TOE-S616-60.1.book 76 ージ 017年8月4日 金曜日 午後3時41

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the YASKAWA Varispeed G7 Series and is the answer not in the manual?

YASKAWA Varispeed G7 Series Specifications

General IconGeneral
BrandYASKAWA
ModelVarispeed G7 Series
CategoryInverter
LanguageEnglish

Related product manuals