6
-88
Motor Overload (OL1) Pre-alarm (Setting: 1F)
This output function is valid when the motor overload protection function is enabled (L1-01 =1).
This output can be used to warn of overheating before the protection function itself operates.
Inverter Overheat (OH) Pre-alarm (Setting: 20)
This output function indicates that the temperature of the cooling fins reaches the temperature set in L8-02
(the Inverter overheating alarm detection level).
Speed reference limit (Setting: 31)
Zero-servo End (Setting: 33)
This output function indicates that zero-servo position control has been completed.
The output is turned ON after the zero-servo command is input and the difference between the zero-servo
operation starting position and the current position is within the zero-servo completion width (b9-02).
OFF The motor protection function's electronic thermal value is less than 90% of the detection level.
ON The motor protection function's electronic thermal value is greater than 90% of the detection level.
OFF The cooling fin temperature is less than the "OH Pre-Alarm Level" set in L8-02.
ON The cooling fin temperature exceeds the "OH Pre-Alarm Level" set in L8-02.
OFF Other than ON condition
ON
Enables the speed reference limit in the following conditions (During flux vector control method):
1. Frequency reference Frequency reference upper limit (d2-01)
Frequency reference Frequency reference lower limit (d2-02)
Frequency reference Output frequency lower limit of the multi-function analog input
(Setting: 9)
2. The frequency reference is less than the Min. output frequency (E1-09), and b1-05 is set to 1,
2, or 3.
OFF The zero-servo command isn't being input or zero-servo position control hasn't been completed.
ON
The position has been brought within the zero-servo completion width (b9-02) after the zero-servo
command was input.
TOE-S616-60.1.book 88 ージ 017年8月4日 金曜日 午後3時41

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the YASKAWA Varispeed G7 Series and is the answer not in the manual?

YASKAWA Varispeed G7 Series Specifications

General IconGeneral
BrandYASKAWA
ModelVarispeed G7 Series
CategoryInverter
LanguageEnglish

Related product manuals