6
-102
0028H Torque reference (U1-09)
0029H Not used
002AH Not used
002BH
Sequence input status
Bit 0 1: Control circuit terminal S1 ON
Bit 1 1: Control circuit terminal S2 ON
Bit 2 1: Control circuit terminal S3 ON
Bit 3 1: Control circuit terminal S4 ON
Bit 4 1: Control circuit terminal S5 ON
Bit 5 1: Control circuit terminal S6 ON
Bit 6 1: Control circuit terminal S7 ON
Bit 7 1: Control circuit terminal S8 ON
Bit 8 1: Control circuit terminal S9 ON
Bit 9 1: Control circuit terminal S10 ON
Bit A 1: Control circuit terminal S11 ON
Bit B 1: Control circuit terminal S12 ON
Bits C to F Not used
002CH
Inverter status
Bit 0
Operation 1: Operating
Bit 1
Zero-speed 1: Zero-speed
Bit 2
Frequency matching 1: Matched
Bit 3
User-defined speed matching 1: Matched
Bit 4
Frequency detection 1 1: Output frequency L4-01
Bit 5
Frequency detection 2 1: Output frequency L4-01
Bit 6
Inverter startup completed 1: Startup completed
Bit 7 Low voltage detection 1: Detected
Bit 8
Baseblock 1: Inverter output baseblock
Bit 9
Frequency reference mode 1: Not communications 0: Communications
Bit A
Run Command mode 1: Not communications 0: Communications
Bit B
Overtorque detection 1: Detected
Bit C
Frequency reference lost 1: Lost
Bit D Retrying error 1: Retrying
Bit E Error (including MEMOBUS communications time-out) 1:Error occurred
Bit F MEMOBUS communications time-out 1: Timed out
002DH
Multi-function contact output status
Bit 0 Multi-function contact output (terminal M1-M2) 1: ON 0: OFF
Bit 1 Multi-function PHC output 1 (terminal P1 - PC) 1: ON 0: OFF
Bit 2 Multi-function PHC output 2 (terminal P2 - PC) 1: ON 0: OFF
Bit 3 Multi-function PHC output 3 (terminal P3 - C3) 1: ON 0: OFF
Bit 4 Multi-function PHC output 4 (terminal P4 - C4) 1: ON 0: OFF
Bits 5 to F Not used
002EH - 0030H Not used
0031H Main circuit DC voltage
0032H Torque monitor (Unit: 1/0.1%)
0033H Output power (U1-08)
0034H - 0037H Not used
0038H PID feedback quantity (Input equivalent to 100%/Max. output frequency; 10/1%; without sign)
0039H PID input quantity (±100%/±Max. output frequency; 10/1%; with sign)
003AH PID output quantity (±100%/±Max. output frequency; 10/1%; with sign)
003BH CPU software number
003CH Flash software number
Register No. Contents
TOE-S616-60.1.book 102 ページ 017年8月4日 金曜日 午後3時41分

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the YASKAWA Varispeed G7 Series and is the answer not in the manual?

YASKAWA Varispeed G7 Series Specifications

General IconGeneral
BrandYASKAWA
ModelVarispeed G7 Series
CategoryInverter
LanguageEnglish

Related product manuals