• Digital Setting Using the Digital Operator
Input the frequency while FREF is lit (press ENTER after setting the
numeric value).
Frequency reference setting is effective when 1 (Factory setting: 0) is
set for constant n009 instead of pressing ENTER.
n009 =0: Enables frequency reference setting using the ENTER key.
=1: Disables frequency reference setting using the ENTER key.
REMOTE Mode
Select the command method in constant n004.
n004 =0: Enables frequency reference setting using the potentiometer
on the Digital Operator.
=1: Enables using frequency reference 1 (n024) (factory setting)
Factory setting of models with the Digital Operator with a
potentiometer (JVOP-140) is n004=0.
=7: Enables a voltage reference on Digital Operator circuit
terminal (0 to 10)
=8: Enables current reference on Digital Operator circuit
terminal (4 to 20mA)
=9: Enables DeviceNet communications.