EasyManua.ls Logo

YASKAWA Varispeed V7 - Jump Frequencies (n083 to n086); Continuing Operation Using Automatic Retry Attempts (n082)

YASKAWA Varispeed V7
256 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
148
Frequency Detection 2
Output frequency Frequency Detection Level n095
(Set n057, n058 or n059 to 5.)
Jump Frequencies (n083 to n086)
This function allows the prohibition or “jumping” of critical frequencies
so that the motor can operate without resonance caused by the machine
system. This function is also used for dead band control. Setting the val-
ues to 0.00 Hz disables this function.
Set prohibited frequencies 1, 2, and 3 as follows:
Operation is prohibited within the jump frequency ranges.
However, the motor will operate without jumping during acceleration/
deceleration.
Continuing Operation Using Automatic Retry Attempts (n082)
When the fault retry function is selected, stand clear of
the Inverter or the load. The Inverter may restart sud-
denly after stopping.
(Construct the system to ensure safety, even if the
Inverter should restart.) Failure to observe this warn-
ing may result in injury.
Release
width
+2Hz
Frequency
Detection
Level (Hz)
(n095)
Output
frequency
Frequency
detection
signal
OUTPUT FREQUENCY
FREQUENCY REFERENCE
n083 n084 n085
If this condition is not satisfied,
the Inverter will display fo
r
one second and restore the
data to initial settings.
WARNING

Table of Contents

Related product manuals