C2.6 External Output
You may switch the output between Control Output (HOUT) and External Output
(EXOUT) using the EXOUT/OUT parameter.
When EXOUT/OUT is set to 0 (Normal output), the PID computation result or some other
control and computation result is output.
When EXOUT/OUT is set to 1 (External output), the output value specified by the
External Output (EXOUT) parameter is output. EXOUT is not constrained by the upper or
lower output limit.
As an example, a sequence CPU may read the value of HOUT, correct or otherwise
process the value, and then write the processed value to EXOUT.
Table C2.22 Parameters Related to External Output
Data Position Number
Symbol Description Unit Data Range
Default
Value
Attribute
Stored
Loop 1 Loop 2 Loop 3 Loop 4
126 326 526 726 EXOUT/OUT
External/normal output
selection
None
0: Normal output
1: External output
0 RW —
136 336 536 736 EXOUT External output % -5.0 to 105.0% 0 RW —
Do not use the following functions when external output is selected.
- Auto-tuning
- ON/OFF control