A2-6
IM 34M06H62-02E 3rd Edition : Jul.16
,
2015-00
Table A2.4 Instrument Range and Accuracy (for low resolution operation with SW1-1 set to ON) 4/4
Input
Category
Input Type
*1
Instrument Range
Input Type Selector Switch
*3
Software
Setting
Accuracy
*4
Resolution
*2
SW1-3 SW1-4 SW5
Software setting ON OFF 0
Instrument ranges may be specified by
software using one of the following codes.
Thermocouple
K
*5
-328 to 2498F
ON OFF
1 33 ($21)
2F
*
5
1F
*
5
-328 to 1832F
2 34 ($22)
2F
*
5
1F
*
5
-328 to 932F
3 35 ($23)
2F 1F
J
-328 to 2192F
4 36 ($24)
2F 1F
-328 to 932F
5 37 ($25)
2F 1F
T
-454 to 752F
6 38 ($26)
2F
*
6
1F
B
*
7
32 to 2912F
7 39 ($27)
2F
*
7
1F
*
7
S
*
8
32 to 2912 F
8 40 ($28)
2F
*
8
1F
R
*
8
32 to 2912F
9 41 ($29)
2F
*
8
1F
N
-328 to 2372F
A 42 ($2A)
2F
*
9
1F
E
-454 to 1832F
B 43 ($2B)
2F
*
10
1F
*
10
L
-328 to 1652F
C 44 ($2C)
2F 1F
U
-328 to 752F
D 45 ($2D)
2F 1F
W
*
11
32 to 2912F
E 46 ($2E)
2F 1F
Platinel 2
32 to 2534F
F 47 ($2F)
2F 1F
RTD
JPt100
-328 to 932F
ON ON
0 48 ($30)
2F 1F
-328 to 392F
1 49 ($31)
2F 1F
32 to 572F
2 50 ($32)
2F 1F
32 to 302F
3 51 ($33)
2F 1F
Pt100
-328 to 1562F
4 52 ($34)
2F 1F
-328 to 932F
5 53 ($35)
2F 1F
-328 to 392F
6 54 ($36)
2F 1F
32 to 572F
7 55 ($37)
2F 1F
32 to 302F
8 56 ($38)
2F 1F
*1: Applicable standard is JIS/IEC/DIN (ITS-90) for thermocouples and RTD.
*2: For thermocouples K, B, S, R, and W, input ranges may be set wider than their instrument range (see the notes below). Furthermore, the
actual range for an acceptable input is the input range5%.
*3: When you turn on the power after changing the hardware switch settings, data stored in the EEPROM is initialized to follow the switch
settings.
*4: This accuracy applies if the ambient temperature is 77F9F and the input value is within the instrument range. If the input type is
thermocouple and reference junction compensation is used, you should also take into consideration the accuracy of the reference
junction compensation.
*5: For K-type thermocouples, the upper and lower input range limits may be set from -454 to 2498F. The accuracy and resolution depend
on measured temperatures as follows:
-454 to 328F: Neither accuracy nor resolution is guaranteed.
*6: For T-type thermocouples, the accuracy and resolution depend on measured temperatures as follows:
-454 to -328F: 7F accuracy, 1F resolution
*7: For B-type thermocouples, the upper and lower input range limits may be set from 32 to 3272F. The accuracy and resolution depend on
measured temperatures as follows:
32 to 572F: Neither accuracy nor resolution is guaranteed.
572 to 1652F: 5F accuracy, 1F resolution
*8: For S-type and R-type thermocouples, the upper and lower input range limits may be set from 32 to 3092F. The accuracy and
resolution depend on measured temperatures as follows:
32 to 392F: 3F accuracy, 1F resolution
*9: For N-type thermocouples, the accuracy and resolution depend on measured temperatures as follows:
-328 to 32F: 4F accuracy, 1F resolution
*10: For E-type thermocouples, the detailed accuracy and resolution are as follows:
-454 to 328F: 12F accuracy, 4F resolution
-328 to 148F: 3F accuracy, 1F resolution
*11: For W-type thermocouples, the upper and lower input range limits may be set from 32 to 4172F.