EasyManuals Logo

York EX Series User Manual

York EX Series
176 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #166 background imageLoading...
Page #166 background image
JOHNSON CONTROLS
166
FORM 155.32-ICOM1.EN.GB
ISSUE DATE: 10/13/2017
SECTION 8 – TROUBLESHOOTING
TABLE 42 - TROUBLESHOOTING THE HIGH
TEMPERATURE GENERATOR
ITEM CAUSE COUNTERMEASURE
1
Cooling water is insufcient
or suspended.
See if the cooling water supply rate conforms to the specication. (Check the ow
meter, discharge pressure of the cooling water pump, current, etc.)
If the ow rate is insufcient, check the opening ratio of the ow controller valve
and check the strainer for clogging.
2
Cooling water temperature
at inlet is high.
Check the capacity of the cooling tower.
3
Non-condensable gas stays
in the machine.
• Check the capacity of the vacuum pump.
• Check the purge unit.
• Purge air from the chiller-heater (See SECTION 7 – MAINTENANCE).
If partial load operation continues for a long period, non-condensable gas tends
to stay in the absorber. In this case, purge directly from the absorber. Use the
instructions shown in SECTION 7 – MAINTENANCE).
4
Heat exchange tube is dirty
(chilled/hot water, cooling
water).
Contact your local Johnson Controls Service Ofce.
5 Solution is crystallized.
6 Corrosion inhibitor is worn.
7
Air leaks in absorption
chiller-heater.
TABLE 43 - REFRIGERANT OVERCOOLING RELAY
ITEM CAUSE COUNTERMEASURE
1
Chilled/hot water ow rate
lowers or changes sharply.
See if the chilled/hot water ow rate changes sharply (particularly in the case
of variable ow rate specication).
If it changes sharply, apply a limit of the change rate to the chilled/hot ow
control or take another measure.
2
Cooling water temperature
at inlet changes sharply.
See if the cooling water temperature at inlet changes sharply (by checking
start and stop of the fan).
If the chiller-heater refrigerant temperature is low, the chiller-heater stops
immediately but does not perform the diluting operation. If left as it is, the
solution may be crystallized in 4-5 hours. To prevent this, dilute the solution
according to the information shown in Manual Refrigerant Blow Down and
Diluting Method on page 142.
3 Load lowers sharply. See if the load changes sharply.
4
Refrigerant is dirty
(contains solution).
See if the refrigerant rening operation has been performed periodically. For
the refrigerant rening method, see Refrigerant Rening Method on page
142.
5
Heat exchange tube is
dirty (Chilled/hot water).
Contact your local Johnson Controls Service Ofce.
6
Temperature controller or
safety switch is broken.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the York EX Series and is the answer not in the manual?

York EX Series Specifications

General IconGeneral
BrandYork
ModelEX Series
CategoryChiller
LanguageEnglish

Related product manuals