SECTION 8 – TROUBLESHOOTING
FORM 155.32-ICOM1.EN.GB
ISSUE DATE: 10/13/2017
8
FIGURE 67 - TROUBLESHOOTING SEQUENCE FLOW CHART
Emergency stop
Audible alarm
(buzzer) “ON”
Dilution operation time
calculation
Chilled water
and/or refrigerant
temp. low cut-out
Dilution Finish
Operation interlock
Cooling water pump interlock
Constantly monitoring interlock
Combustion monitoring interlock
Low cooling water inlet temperature
HG high temperature / high pressure
High cut
High exhaust gas temperature
Flame failure
Fuel line abnormal
HG low liquid level
Burner fan / Oil pump abnormal
Control sensor abnormal
CPU abnormal
Failure indicator
light “ON”
1
1
Yes
Yes
No
No
No
Yes
Reset operation
(buzzer “OFF”)
External outlet
issues
No
Yes
Dilution operation
complete
Stop dilution
operation?
Yes
Damper fully closed
Burner stop
Dilution operation time
integration
Solution refrigerant
pump stop
Dilution operation time
integration stop
Solution and refrigerant
pump continue to
operate
Solution pump and
refrigerant pump stop
Chilled/hot water
cooling water pump
stop
HT- Gen.
pressure low
Air conditioner and
cooling tower fan stop
Dilution
operation more than
30 minutes.
No
Chilled/hot water suspension
Chilled water overcooled
• High hot water temperature
• Emergency failure interlock.
Cooling water suspension
(Option)
Solution circulation pump
abnormal
Solution spray pump
abnormal
Refrigerant pump abnormal
Solution pump inverter
abnormal