SECTION 5 - COMMISSIONING
JOHNSON CONTROLS
5
FORM 155.32-CL1
ISSUE DATE: 03/31/2017
DIRECT FIRED ABSORPTION CHILLER-HEATER COMMISSIONING DATA SHEET (1/3)
User:
Model: MFG.No.: User's machine code:
Insulation Resistance Electric Power Supply
Standard: 5 MΩ or more (with 500 V meg-
ger)
R-Gnd S-Gnd T-Gnd
Specication: AC
V / Hz
Circuit breaker MΩ Standard: Within +/- 10% of spec.
R-S V
U-Gnd V-Gnd W-Gnd R-T V
Solution circulation pump MΩ S-T V
Solution spray pump MΩ R-Gnd V
Refrigerant pump MΩ S-Gnd V
Purge pump MΩ T-Gnd V
Thermal Relay Setting Refrigerant Purity Temperature Setting
Solution circulation pump A Standard: 1.040 (kg/L) or less Cooling
Solution spray pump A Specic gravity Set base temp. °C
Refrigerant pump A Turbidity Auto. stop temp °C
Purge pump A Auto restart diff. °C
Heating
Pump Discharge Pressure Purge Amount Set base temp. °C
Solution circulation pump MPa.G Standard: 4 cc/min or less Auto. stop temp. °C
Solution spray pump MPa.G Purge tank cc Auto. restart diff. °C
Refrigerant pump MPa.G Absorber cc
NOTES:
________________________________________________________________
________________________________________________________________
________________________________________________________________
________________________________________________________________
________________________________________________________________
________________________________________________________________