SECTION 5 - COMMISSIONING
JOHNSON CONTROLS
7
FORM 155.32-CL1
ISSUE DATE: 03/31/2017
DIRECT FIRED ABSORPTION CHILLER-HEATER COMMISSIONING DATA SHEET (3/3)
User:
Model: MFG.No.: User's machine code:
Running Data
Date: Measured by Specification Standard : : :
Fuel
Output Valve % Control panel
Exhaust gas temperature °C Control panel ≤ 250°C
Fuel Consumption Flow meter
Chilled/Hot
Water
Inlet temperature °C Control panel
Outlet temperature °C Control panel
Inlet pressure Pressure gauge
Outlet pressure Pressure gauge
[3] Pressure drop DPG or calculation [4]
[1] Flow rate FM or calculation [2]
Cooling
Water
Inlet temperature °C Control panel 20.0~32.0°C
Outlet temperature °C Control panel 20.0~37.5°C
Inlet pressure Pressure gauge
Outlet pressure Pressure gauge
[7] Pressure drop DPG or calculation [8]
[5] Flow rate FM or calculation [6]
Absorption
Cycle
HG pressure (gauge) MPa.G Compound gauge
≤ -0.003
MPa
HG pressure (sensor) kPa.abs Control panel ≤ 94.7 kPa
HG temperature °C Control panel ≤165°C
HG solution concentration % Control panel
Absorber temperature °C Control panel
Refrigerant temperature °C Control panel
Liquid
Level
HG Level gauge
LG Level gauge
Absorber Level gauge
Evaporator (lower) Level gauge
Evaporator (upper) Level gauge
NOTES:
Operating hours________hours
Number of purge times________times
Fill out each specication pressure drop according to the factory inspection report (actual value).
If differential pressure gauge (DPG) is not available, calculate each pressure drop.
If ow meter (FM) is not available, calculate each ow rate as below.
[1] = [2] x √[3] / [4] [5] = [6] x √[3] / [4]
LD20020
Height
OUT
P P
IN