SECTION 5 – TECHNICAL DATA
FORM 150.73-NM1
ISSUE DATE: 09/04/2020
55
Electrical Data
TABLE 9 - VOLTAGE RANGE
VOLTAGE RANGE
VOLTAGE CODE UNIT POWER MINIMUM MAXIMUM
-17 200-3-60 180 220
-28 230-3-60 207 253
-40 380/415-3-60 342 440
-46 460-3-60 414 506
-50 380/415-3-50 342 440
-58 575-3-60 517 633
TABLE 8 - MICRO PANEL POWER SUPPLY
UNIT VOLTAGE
UNIT
VOLTAGE
CONTROL
POWER
MCA
NOTE A
OVER CURRENT PROTECTION,
SEE NOTE B
NF DISC SW
MINIMUM MAXIMUM
MODELS W/O
CONTROL
TRANS
115-1-60/50
15A 10A 15A 30 A / 240V
MODELS W/
CONTROL
TRANS
-17 200-1-60 15A 10A 15A 30 A / 240V
-28 230-1-60 15A 10A 15A 30 A / 240V
-40 380-1-60 15A 10A 15A 30 A / 480V
-46 460-1-60 15A 10A 15A 30 A / 480V
-50 380/415-1-60 15A 10A 15A 30A / 415V
-58 575-1-60 15A 10A 15A 30 A / 600V
A. Minimum #14 AWG, 75 °C, Copper Recommended
B. Minimum and Maximum Over Current Protection, Dual Element Fuse or Circuit Breaker
It is possible that multiple sources of
power can be supplying the unit power
panel. To prevent serious injury or death,
the technician should verify that NO
LETHAL VOLTAGES are present inside
the panel AFTER disconnecting power,
before working on equipment.
The unit evaporator heater uses 120 VAC.
Disconnecting 120 VAC power from the
unit, at or below freezing temperatures,
can result in damage to the evaporator
and unit as a result of the chilled liquid
freezing.