Technical data 105
12
Technical data
What this chapter contains
This chapter contains the technical specifications of the drive, for example, the ratings,
sizes and technical requirements, provisions for fulfilling the requirements for CE and other
markings.
Ratings
The nominal ratings for the drive modules with 400 V (50 Hz and 60 Hz) supply are given
below. The symbols are described below the table.
Drive type Frame
size
Input
ratings
Output ratings
Nominal IEC M2/M3 UL NEMA
I
1N
I
2N
I
cont
I
max
IP I P
A AAAAkWA hp
ACQ810-302A-4 G 297 302 340 480 - - 302 250
ACQ810-361A-4 G 355 361 400 568 - - 361 300
ACQ810-414A-4 G 407 414 430 588 354 200 414 350
ACQ810-477A-4 G 459 477 521 588 448 250 477 400
ACQ810-550A-4 G 531 550 602 840 550 315 515 450
ACQ810-616A-4 G 599 616 693 1017 616 355 590 500
ACQ810-704A-4 G 689 704 720 1017 700 400 704 600
00581898
I
1N
Nominal input current (rms)
I
2N
Nominal output current. 110% overload is allowed for 1 minute every 5 minutes.
I
cont
Continuous rms output currents with no overload capability
I
max
Maximum output current. Available for 10 seconds at start, otherwise as long as allowed by drive
temperature.
P Typical motor power