Electrical installation 75
Motor cable connection procedure
1. Connect the twisted shield of the motor cable to the grounding terminal with a cable
lug.
2. Connect the phase conductors to the cable lug terminals U2, V2 and W2.
It is recommended to ground the motor cable shield 360° at the cabinet cable entry, see
page 37.
For minimum radio frequency interference, ground the motor cable shield at the motor end
as follows:
360 degrees at the lead-through of the motor terminal box
1
2
1
2
V2
U2
W2
360 degrees grounding