EasyManua.ls Logo

ABB ACQ810 - Quick Guide for Selecting between Gg and Ar Fuses; Fuses (UL)

ABB ACQ810
134 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
110 Technical data
Quick guide for selecting between gG and aR fuses
The table below is a short cut in selecting between gG and aR fuses. The combinations
(cable size, cable length, transformer size and fuse type) in the table fulfill the minimum
requirements for the proper operation of the fuse.
The following parameters can affect the correct operation of the protection:
cable length ie, the longer the cable the weaker the fuse protection, as the long cable
limits the fault current
cable size ie, the smaller the cable cross-section the weaker the fuse protection, as
the small cable size limits the fault current
transformer size ie, the smaller the transformer the weaker the fuse protection, as the
small transformer limits the fault current
transformer impedance ie, the higher the z
k
the weaker the fuse protection as high
impedance limits the fault current.
The protection can be improved by installing a larger supply transformer and/or bigger
cables, and in most cases by selecting aR fuses instead of gG fuses. Selection of smaller
fuses improves the protection, but may also affect the fuse life time and lead to
unnecessary operation of the fuses.
In case of any uncertainty regarding the drive protection, please contact your local ABB
representative.
Fuses (UL)
UL class T or L fuses for branch circuit protection per NEC are listed below. Fast acting
class T or faster fuses are recommended in the USA.
Check from the fuse time-current curve that the operating time of the fuse is below
0.1 seconds. The operating time depends on the supply network impedance and the
cross-sectional area and length of the supply cable. The short-circuit current can be
calculated as shown on page 107.
Drive type
ACQ810-
04…
Cable type Supply transformer minimum apparent power S
N
(kVA)
Copper Aluminum Maximum cable length with
gG fuses
Maximum cable length with
aR fuses
10 m 50 m 100 m 10 m 100 m 200 m
-302A-4 2 × (3x120) Cu 3 × (3x95) Al 530 570 670 370 370 370
-361A-4 2 × (3x120) Cu 3 × (3x95) Al 530 570 670 370 370 370
-414A-4 2 × (3x120) Cu 3 × (3x95) Al 530 570 670 370 370 370
-477A-4 3 × (3x95) Cu 3 × (3x150) Al 660 720 840 500 570 760
-550A-4 3 × (3x120) Cu 3 × (3x185) Al 660 720 840 520 570 760
-616A-4 2 × (3x240) Cu 3 × (3x240) Al 880 980 1200 580 670 880
-704A-4 3 × (3x150) Cu 3 × (3x240) Al 880 980 1200 610 670 880
Note 1: The supply transformer minimum power in kVA is calculated with a z
k
value of 6% and frequency
50 Hz.
Note 2: The table is not intended for transformer selection - that must be done separately.
00556489 A

Table of Contents

Other manuals for ABB ACQ810

Related product manuals