ACS 160 Users Manual 91
Figure 23 Sleep function operation.
4019 SET POINT SEL
Set point selection. Defines the reference signal source for the PID controller.
Note! When PID regulator is by-passed (parameter 8121
REG BYPASS CTRL), this parameter has no
significance.
1 =
INTERNAL
Process reference is a constant value set with parameter 4020 INTERNAL SETPNT.
2 =
EXTER NAL
Process reference is read from a source defined with parameter 1106 EXT REF2 SELECT. The ACS 160 must
be in remote mode (REM is shown on control panel display).*
* Process reference to PID controller can also be given from the control panel in local mode (LOC is shown
on control panel display) if the panel reference is given as percentage, i.e. value of parameter 1101
KEYPAD
REF SEL = 2 (REF2 (%)).
4020 INTERNAL SETPNT
Sets a constant process reference (%) for the PID controller. PID controller follows this reference if
parameter 4019
SET POINT SEL is set to 1 (INTERNAL).
Code Description
PID input (Process actual value)
Time
Time
PID Output (Output frequency)
Wake-up level
SLEEP
LEVEL
parameter 4014
STOP START
t
d
=
SLEEP
DELAY
, parameter 4013
t < t
d
t
d
WAKE-UP DELAY
parameter 4017