36 ACS 160 User’s Manual
Application Macro ABB Standard
This general purpose macro is typical 2-wire I/O configuration. It gives two more preset speeds
compared to Factory Macro (0).
The value of parameter 9902 is 1 (
ABB STANDARD).
Connection Example:
*Constant speed selection: 0 = open, 1 = connected
ABB Standard default parameter values:
Input signals Output signals DiP switch
• Start, stop and direction
(DI1,2)
• An. output AO: Frequency
• Analogue reference (AI1) • Relay output 1: Fault
• Preset speed selection (DI3,4) • Relay output 2: Running
• Ramp pair 1/2 selection (DI5)
DI3 DI4 Output
00Reference through AI1
10Const speed 1 (1202)
01Const speed 2 (1203)
11Const speed 3 (1204)
1001
EXT 1 COMMANDS 2 (DI1,2) 1201 CONST SPEED SEL 7 (DI3,4)
1002
EXT 2 COMMANDS 0 (NOT SEL) 1402 RELAY OUTPUT 22 (RUN)
1003
DIRECTION 3 (REQUEST) 1601 RUN ENABLE 0 (NOT SEL)
1102
EXT1/EXT2 SEL 6 (EXT1) 1604 FAULT RESET SEL 0 (KEYPAD)
1103
EXT REF1 SELECT 1 (AI1) 2105 PREMAGN SEL 0 (NOT SEL)
1106
EXT REF2 SELECT 0 (KEYPAD) 2201 ACC/DEC 1/2 SEL 5 (DI5)
AI1:
AI2:
0 - 10 V
0(4) - 20 mA
NO
NO
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
SCR
AI1
AGND
+10V
AI2
AGND
AO1
AGND
+24V
DCOM
DI1
DI2
DI3
DI4
DI5
RO1B
RO2A
RO2B
RO1A
mA
External Reference 1: 0...10 V <=> 0...50 Hz
Reference voltage 10 VDC
Not used
Output frequency 0...20 mA <=> 0...50 Hz
+24 VDC
Start/Stop: Activate to start
Fwd/Rev: Activate to reverse rotation direction
Constant speed selection*
Constant speed selection*
Ramp pair selection. Activate to select ramp pair 2.
Relay output 1, programmable
Default operation: Fault => open
Relay output 2, programmable
Default operation: Running => closed