ACS 160 Users Manual 37
Application Macro 3-wire
This macro is intended for those applications where the drive is controlled using momentary push-
buttons. It gives two more preset speeds compared to Factory Macro (1) by using DI4 and DI5.
The value of parameter 9902 is 2 (3-
WIRE).
Connection example:
*Constant speed selection: 0 = open, 1 = connected
Note! Stop input (DI2) deactivated: panel START/STOP button interlocked (local).
3-wire default parameter values:
Input signals Output signals DIP switch
Start, stop and direction
(DI1,2,3)
An. output AO: Frequency
Analogue reference (AI1) Relay output 1: Fault
Preset speed selection (DI4,5) Relay output 2: Running
DI4 DI5 Output
00Reference through AI1
10Constant speed 1 (1202)
01Constant speed 2 (1203)
11Constant speed 3 (1204)
1001
EXT 1 COMMANDS 4 (DI1P,2P,3) 1201 CONST SPEED SEL 8 (DI4,5)
1002
EXT 2 COMMANDS 0 (NOT SEL) 1402 RELAY OUTPUT 22 (RUN)
1003
DIRECTION 3 (REQUEST) 1601 RUN ENABLE 0 (NOT SEL)
1102
EXT1/EXT2 SEL 6 (EXT1) 1604 FAULT RESET SEL 0 (KEYPAD)
1103
EXT REF1 SELECT 1 (AI1) 2105 PREMAGN SEL 0 (NOT SEL)
1106
EXT REF2 SELECT 0 (KEYPAD) 2201 ACC/DEC 1/2 SEL 0 (NOT SEL)
AI1:
AI2:
0 - 10 V
0(4) - 20 mA
NO
NO
External Reference 1: 0...10 V <=> 0...50 Hz
Reference voltage 10 VDC
Not used
Output frequency 0...20 mA <=> 0...50 Hz
+24 VDC
Momentary activation with DI2 activated: Start
Momentary deactivation: Stop
Fwd/Rev: activate to reverse rotation direction
Constant speed selection*
Relay output 1, programmable
Default operation: Fault => open
Relay output 2, programmable
Default operation: Running => closed
Constant speed selection*
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
SCR
AI1
AGND
+10V
AI2
AGND
AO1
AGND
+24V
DCOM
DI1
DI2
DI3
DI4
DI5
RO1B
RO2A
RO2B
RO1A
mA