ACS 160 Users Manual 69
Group 16: System Controls
Code Description
1601 RUN ENABLE
Selects the source of the run enable signal.
0
= NOT SEL
The ACS 160 is ready to start without an external run enable signal.
1...5 = DI1 ... DI5
To activate the run enable signal, the selected digital input must be activated. If the voltage drops and
deactivates the selected digital input, the ACS 160 will coast to stop and not start until the run enable signal
resumes.
6 =
COMM
The run enable signal is given through serial communication (Command Word bit #3).
1602 PARAMETER LOCK
Parameter lock for control panel.
0 =
LOCKED
Parameter modification disabled.
1 =
OPEN
Panel operations are allowed and parameter modification is enabled.
Note! This parameter is not affected by macro selection.
1604 FAULT RESET SEL
Fault reset source.
Note! Fault reset is always possible with control panel.
Note! Option 6 (
START/STOP) should not be selected when start, stop and direction commands are given
through serial communication.
0 =
KEYPAD
Fault reset is executed from the control panel keypad.
1...5 = DI1 ... DI5
Fault reset is executed from a digital input. Reset is activated by deactivating the input.
6 =
START/STOP
Fault reset is activated by Stop command.
7 =
COMM
Fault reset is executed through serial communication.
1605 LOCAL LOCK
Local lock. When
LOCAL LOCK is active (1=LOCKED), the drive cannot be changed from remote mode to local
mode.
0 =
OPEN
Control location can be changed from control panel.
1 =
LOCKED
Panel cannot change to local mode.
Note! Option 1
LOCKED can be selected only in remote mode.
1608 DISPLAY ALARMS
Controls the visibility of some of the alarms, see Diagnostics.
0 =
NO
Some of the alarms are suppressed.
1 =
YES
All of the alarms are enabled.