06 ELECTRICAL INSTALLATION
3BHS799208 E01 REV E ACS5000 WATER-COOLED USER MANUAL 102/186
Figure 6-9 Cable entry frame sizes (top) for type 1 sealing modules (bottom)
Table 6-1 Type 1 sealing modules and cables per frame opening
Frame 1 1 2 3 4 5 6A 6B
Location COU PCU PCU PCU PCU EXU SBU SBU
Cable entry
top
FS 2/4/6 FS 2/4/6 FS 1/3/5 - -
√ √ √
Cable entry
bottom
FS 2/4/6 FS 2/4 FS 1/3 FS 6 FS 5
√ √ √
Table 6-2 Maximum number of type 1 sealing modules per frame opening
Frame 1 1 2 3 4 5 6A 6B
RM120 2 2 2 1 1 1 2 1
RM90 - - - - - 2 2 1
RM60 8 8 8 4 4 6 8 4
Table 6-3 Maximum number of cables per frame opening - 3 core
Frame 1 1 2 3 4 5 6A 6B
∅ 68-99 mm 2 2 2 1 1 1 2 1
∅ 48-71 mm - - - - - 2 2 1
Table 6-4 Maximum number of cables per frame opening - single core
Frame 1 1 2 3 4 5 6A 6B
∅ 28-50 mm 8 8 8 4 4 6 8 4
L1 L2
L3
L1 L2
L3
L1
RM120
Frame sizes (FS)
RM60RM69
A
B
1
2
3 4
5
6
6