3BHS799208 E01 REV E ACS5000 WATER-COOLED USER MANUAL 115/186
06 ELECTRICAL INSTALLATION
6.8.1.2 Preparing cables for cable entries with cable glands
Prepare the cables with an outer cable screen for EMC bonding with the
metal enclosure of the cabinet as illustrated.
Figure 6-20 Preparing control cables for cable glands
6.8.2 Connecting the cables
For information on project-specific connections, see Appendix D
Wiring diagrams.
For information on terminal sizes, see document
Customer interface.
(1) Outer cable sheath
(2) Cable gland
(3) Conductor insulation removed to
expose cable shield
(4) Plate
(5) Conductor screen extension to be
connected to PE terminal
1
2
3
4
5