06 ELECTRICAL INSTALLATION
3BHS799208 E01 REV E ACS5000 WATER-COOLED USER MANUAL 92/186
6.3 Cable requirements
6.3.1 Power cables
For information on the requirements for power cables, ground cable and
equipotential bonding conductor, see:
ACS5000 power cable specification
Power cables engineering guideline
6.3.2 Auxiliary and control cables
Note: For information on the requirements for the auxiliary power cable
and the control cables, see Auxiliary power and control cables guideline
NOTICE
Risk of false signals!
DO NOT lay control cables in parallel to the power supply cables.
If this cannot be avoided, a minimum distance of 30 cm must be
maintained between control and power supply cables.
Cross control and power supply cables at an angle of 90°