3BHS799208 E01 REV E ACS5000 WATER-COOLED USER MANUAL 87/186
05 MECHANICAL INSTALLATION
5.13 Joining busbars
There are three types of busbars that need to be joined:
AC busbars (Fig. 5-10: 1)
PE ground busbar (Fig. 5-10: 2)
DC busbars (Fig. 5-10: 3)
Figure 5-10 Busbar connections
1. Before installing the joining pieces, grease the bolts to maintain the
required contact pressure.
2. Join the busbars.
3. Tighten the bolts to the torque of 40 Nm.
1
2
3