3BHS799208 E01 REV E ACS5000 WATER-COOLED USER MANUAL 133/186
08 OPERATION
8.8 Stopping the drive
To stop the motor, press the STOP key.
The motor stops according to the preset stop function. While the
motor stops, the status line of the display shows ReadyRef and the run
status message blinks.
As long as the stop sequence is in progress, you can always restart the
drive by pressing the START key.
Just before the motor comes to a standstill, the status line shortly
displays Stopping.
When the motor has reached zero speed, the status line
displays ReadyRun.
As long as the MCB has not been opened, you can restart the motor at
any time.
I0
1 L -> 600.0 rpm I
StateINU ReadyRef
MOTOR SP 300.00 rpm
POWER 20.0 kW
LOC RESET REF
REM
1 L -> 600.0 rpm 0
StateINU Stopping
MOTOR SP 0.00 rpm
POWER 0.0 kW
1 L -> 600.0 rpm 0
StateINU ReadyRun
MOTOR SP 0.00 rpm
POWER 0.0 kW