06 ELECTRICAL INSTALLATION
3BHS799208 E01 REV E ACS5000 WATER-COOLED USER MANUAL 108/186
6.7.2 Connecting the cables
6.7.2.1 Checking the cable insulation
Measure the insulation of each cable before connection and verify
that the results are within the specification of the cable
manufacturer.
Leave the conductors unconnected at both ends until the
commissioning personnel has given permission to connect them.
CAUTION
Risk of flashover!
High voltages will be present in the terminal compartment. High voltages
can cause flashover between conductors with different electric potential,
and between a conductor and earth.
Therefore, route and connect the cables in such a way that the following
minimum clearances are maintained:
70 mm between cable lugs of conductors with a different potential
70 mm between the cable lug of a conductor and the parts with
earth potential
30 mm between cables with a different potential