06 ELECTRICAL INSTALLATION
6.7.1.3 Preparing cables for cable entries with sealing modules
• Prepare cables with an outer cable screen or shield for EMC bonding 
with the metal enclosure of the cabinet as illustrated.
Figure 6-14 Preparing power cables for sealing modules
• Install the sealing modules according to the instructions of the 
sealing module supplier.
(1) Sealing module
(2) Frame
(3) Conductive foil of sealing module
(4) Cable clamp
(5) Shrinkable sheath seal
(6) Heat-shrinkable termination
(7) Outer cable sheath
(8) Cable sheath removed to expose 
cable shield
(9) Shield extension to be connected 
to PG busbar
(10) Cable screen extension to be 
connected to the PG busbar
(11) Cable lug as specified by the cable 
supplier and suitable for M12 bolt
(12) Sheath seal