06 ELECTRICAL INSTALLATION
3BHS799208 E01 REV E ACS5000 WATER-COOLED USER MANUAL 118/186
Control power supply
Connect the cable for the control power to terminal X2
(Fig. 6-23: 11).
Control signals
Connect the cables to the following terminals:
- X10, X11 (Fig. 6-23: 10)
Main circuit breaker signals and emergency off signals
- X20 X27 (Fig. 6-23: 7)
Control signals of monitored equipment
Fieldbus interface
Connect the cable directly to the fieldbus adapter.
Encoder interface
1. Connect the cable directly to the encoder adapter.
2. Connect the overall shield and the individual shields of the encoder
cable to the copper busbar.
IMPORTANT! DO NOT connect the shields directly to the encoder adapter.