64
…4 CONFIGURATION MODE
C10...C14
0.0
r2L
C.14
NONE
AN2.A
C.10
20.0
AN2H
C.11
4.0
AN2.L
C.12
100.0
r2H
C.13
rLY1
NONE
•1
•1
•1
•1
•1
•2
•2
dG1.P
0.0
r1L
0.0
4.8.3 Analog Output 2
Analog Output 2 (ao2) Assignment Source
Select the source required to activate Analog Output 2.
See Rear Fold-out/ Table D – Analog Sources.
Analog Output 2 (ao2) Electrical High
The maximum current output required for the retransmission range.
[0.0 to 20.0mA]
Analog Output 2 (ao2) Electrical Low
The minimum current output required for the retransmission range.
[0.0 to 20.0mA]
Retransmission 2 Engineering High
The engineering range value at which maximum output is required.
[In engineering units]
Retransmission 2 Engineering Low
The engineering range value at which minimum output is required.
[In engineering units]
Continued…
•1 If the output is assigned to a control output by the control type, the setting displayed cannot be changed – see
Section 4.2, Basic Configuration/ Control Output Type.
•2 Not applicable if analog output 2 is assigned to a control output.