ControlMaster CM30, CM50 and CMF310
Universal process controllers,
1
/4,
1
/2 DIN and fieldmount 7 Advanced Level
IM/CM/ED–EN Rev. X 67
…Profile Parameters / …Common Settings
Run / Hold Selects the digital source used to start and hold the program. The program runs when
the input is high and holds when the input is low.
Stop Selects the digital source used to stop the program. The program is stopped on the
rising edge.
Skip Segment Selects the digital source used to skip to the next segment. The segment is skipped on
the rising edge.
Repeat Segment Selects the digital source used to repeat the current segment. The segment is repeated
on the rising edge.
Wait Event 1
Wait Event 2
Selects the digital source used to activate Wait Event 1 and Wait Event 2. The program
will enter a wait state when the state of the inputs corresponds with the condition
enabled in the current segment.
Note: Displayed only if Wait Events are enabled.
Next Program Selects the digital source used to activate the Next Program.
Previous Program Selects the digital source used to activate the Previous Program.
Recovery
Action Selects the profile restart action when power is restored after a failure or the PV is
restored after a failure and the Recovery Period (Time – see below) has expired.
Continue
The program resumes from the point at which failure occurred and is placed in
Operator Hold mode.
Repeat
The program resumes from the start of the current segment and is placed in
Operator Hold mode.
Reset
The program resumes from the start of the current program and is placed in
Operator Hold mode.
Advance
The program resumes at the point in the program that would have been reached if no
power failure had occurred in Run mode.
Note. If a zero time period is selected the program will always with the chosen option.
Time Set the recovery time period used to determine the recovery action. The time is
configurable in HH:MM:SS.